I/O Modules
DCP-CZM
CZM CONVENTIONAL ZONE INPUT MODULE
0400-01840
Colour: Ivory
Tone: No
LED Colour: No Light
WEE Compliant: Not in Scope
ROHS Compliant: Not in Scope
- UL 864 9th Edition Listed
- Provides an addressable point for a zone of up to 25 conventional smoke detectors
- Blinks green when being polled by the fire panel
- Latches on red when activated (controlled by panel)
- Device address can be programmed with a handheld programmer. Device address- ranges from 1 to 127
- Compatible with Class A and Class B wiring
- Auxiliary power source required to provide power for the zone of detectors
- Compatible with conventional smoke detectors, SOE-24V, SOE-24H, SOC-24V,SOC-24VN, SLV, SLR, SLK, SIH, SIJ, and conventional heat detectors, DCD, DFE, and DSC
The Conventional Zone Module (DCP-CZM) is designed for use on an analog addressable Fire Alarm system. Up to 127 devices can be placed on a single SLC loop. The device address is uniquely stored on an onboard EEPROM. The module allows the panel to interface and monitor two-wire conventional detectors or pull stations. Each DCP-CZM transmits the status on one zone of devices (25 maximum per zone) back to the panel. It supervises the power supply as well as the entire zone of devices.