I/O Modules
CHQ-DIM2(HFP)-SCI
CHQ-DIM2(HFP)-SCI DUAL INPUT MODULE
1433770-23WEEE Compliant: Not in Scope
ROHS Compliant: Not in Scope
- Single Loop Address
- Loop Powered
- 2 Independent Inputs for Monitoring of Volt Free Contacts
- Each Input can be Configured to Monitor either Normally Open or Normally Closed contacts
- Smart-Fix Housing System for flexibility
- Features an integral SCI
- Approved by LPCB
Model CHQ-DIM2(HFP)-SCI is a Dual Input Module designed to interface to a variety of inputs such as door contacts, sprinkler flow/door switches and plant equipment.
The unit supports a resistive feature for the monitoring of the inputs when operating in Enhanced mode. Please check for panel support of this feature, failure to do so will regress this device into Compatibility mode where the inputs are not monitored.
The unit also features an integral short-circuit isolator.
A back box is also available (CHQ-BACKBOX) which, when used in conjunction with the CHQ-DIM2(HFP)-SCI, increases the IP rating to IP65.
Quantity: