How do I connect a FIREbeam to a Hochiki ESP loop, and when is a CHQ-POM needed for the CDX version?
A FIREbeam normally means the ESP FIREbeam Xtra, which connects straight to the loop. A CHQ-POM is needed only to put a conventional CDX FIREbeam Xtra on an ESP loop, with the loop unpowered while addressing and a panel that supports the CHQ-POM.
Direct answer
An ESP FIREbeam Xtra connects directly to a Hochiki ESP loop and needs no separate CHQ-POM or power supply. A CHQ-POM is needed only to put a conventional CDX FIREbeam Xtra on an ESP loop: one CHQ-POM per beam, with its output set to 22 mA to power the beam and its two monitored inputs reporting the fire and fault relays. In both cases, address the module with a TCH-B200 and PL-3 lead while the loop is unpowered, and use a control panel that supports the CHQ-POM output.
Applies to
- Products / Models: ESP FIREbeam Xtra and ESP FIREbeam (reflective beam smoke detectors with an integral ESP control module); CDX FIREbeam Xtra (conventional reflective beam smoke detector) with the CHQ-POM powered output module; TCH-B200 hand-held programmer and PL-3 programming lead
- Firmware / Version: Not applicable (support for the CHQ-POM depends on the control panel and its configuration software)
- Region: UK / Europe
- Standards: BS EN 54-12 (ESP FIREbeam Xtra, CDX FIREbeam Xtra), BS EN 54-18 (CHQ-POM)
Which arrangement do I have?
- ESP FIREbeam Xtra (and the earlier ESP FIREbeam): this is the beam usually meant by “FIREbeam”. The control module sits on the main PCB inside the head unit and gives the beam full connectivity to the Hochiki ESP loop. The beam takes its power from the loop (supply voltage 17 to 41 V DC; 3.5 mA constant current in all operational states, 17 mA in fast commissioning mode), so do not connect a separate power supply to it, and do not add a separate CHQ-POM.
- CDX FIREbeam Xtra: a conventional beam with a 12 to 30 V DC supply and relay outputs for fire and fault. To put it on an ESP loop, it is powered and monitored through a CHQ-POM, one CHQ-POM per beam.
On the panel, the ESP FIREbeam is configured as a CHQ-POM output. Depending on the panel and its configuration software, the panel may list the beam as a powered output module (one output and two inputs) or as a fire beam.
Check panel compatibility first
The current of the CHQ-POM output is selected from the control panel, so the panel must support the CHQ-POM. The same applies to the ESP FIREbeam Xtra, whose output must be set to 22 mA and kept powered in its normal state. The Hochiki Latitude supports the CHQ-POM output settings as Firebeam device type (current limit, output normally on and drop on reset). If you use the beam with any other panel, and in particular with a panel from another manufacturer, check with the panel manufacturer and Hochiki Europe Technical Support that the panel can handle the CHQ-POM (an ESP protocol output module), set its output current and keep the output powered, because support differs between panels and software versions.
A panel that learns the beam address does not prove that the beam is supported. If the panel cannot set the output current and keep the output powered, the beam receives no supply and does not operate.
Steps: connecting the beam to the loop
- Confirm the panel supports the CHQ-POM. If it does not, use the arrangement in “If the panel does not support the CHQ-POM” below instead.
- Set the address with the loop unpowered. Connect the PL-3 programming lead to the remote programming socket on the TCH-B200, then to the module: on an ESP FIREbeam Xtra, the blue programming socket on the control module inside the head unit; on a CHQ-POM, its programming connector. Program the address and write it on the module label. The loop must not be powered while the address is set. On an ESP FIREbeam Xtra, program the module before you plug the head into its base plate.
- Connect the loop. On an ESP FIREbeam Xtra, wire the loop into the head as shown in the installation manual. On a CHQ-POM, use the wiring terminal block for loop in and loop out. Do not add a separate power supply to an ESP FIREbeam Xtra.
- Wire the CHQ-POM to a CDX FIREbeam Xtra (conventional beam only). Connect the CHQ-POM output (brown +, red −) to the supply terminals of the beam. Connect Input 1 (orange +, yellow −) to the fire relay and Input 2 (green +, blue −) to the fault relay, which is energised in its normal state. Fit the 470 Ω activation resistor and the 10 kΩ EOL resistor supplied with the CHQ-POM on each input, with the 10 kΩ resistor at the far end of the cable from the CHQ-POM, as shown in the CHQ-POM connections drawing. Mount the CHQ-POM next to the beam, and do not remove its PCB from the casing, because this voids the EN 54 approval. The connection drawings show the conventional FIREbeam terminal block; check the terminal names against the installation manual for your beam model.
- Configure the panel. Set the output current to 22 mA, make the output powered in its normal state, and make it change state for at least five seconds on a panel reset. For a CHQ-POM, map Input 1 to fire and Input 2 to fault. The step-by-step configuration, including the dedicated output group, is in Why does my ESP FIREbeam go into fault every time the panel is reset?
- Check loop loading, then commission. Include every beam in the loop loading check for the panel. An ESP FIREbeam Xtra draws 17 mA from the loop in fast commissioning mode instead of 3.5 mA, so if the loop cannot support several beams in fast mode, commission one beam at a time or use normal mode. For a CDX FIREbeam Xtra, the loop supplies the CHQ-POM, whose current depends on the output current set at the panel and whose output stays on in normal operation; ask Hochiki Europe Technical Support how to include it in the loop calculation. Then carry out pre-alignment, alignment and the fire test as described in the installation manual. BS 5839-1 recommends that, unless the equipment compensates for reflections, a beam that uses a reflector is tested at commissioning by partial obscuration of the beam near the reflector.
If the panel does not support the CHQ-POM
Either change to a panel that supports the CHQ-POM, or keep the panel and use a conventional CDX FIREbeam Xtra with its own power supply. Power the beam from a separate supply that conforms to BS EN 54-4, and connect its fire and fault relays to a conventional zone module such as the CHQ-SZM2(SCI), which can monitor one beam detector. The zone module cannot supply enough power to run the beam, so the separate supply is still needed. Ask Hochiki Europe Technical Support for the wiring between the beam relays and the zone module. See Which Hochiki CHQ zone monitor do I need - CHQ-SZM2(SCI) or CHQ-DZM(SCI)? and Which Hochiki CHQ modules need an external 24 V PSU?
The CHQ-POM arrangement is also used for other conventional detectors that need a separate DC supply and have fire and fault relays, such as the IFD-E flame detector. Each device needs its own CHQ-POM.
When to contact technical support
- You plan to use the beam with a panel that is not a Hochiki panel, or the panel manufacturer cannot confirm that the panel supports the CHQ-POM.
- The panel learns the beam but the beam has no power or stays in fault after the configuration has been checked.
- You need the wiring drawing for a specific beam and panel combination, or the installation manual for your beam model.
- You need to include CDX FIREbeam Xtra beams on CHQ-POMs in a loop loading calculation.
State the beam model, the panel make and model, and how the panel lists the beam when you contact Hochiki Europe Technical Support.
Safety note
This article is general guidance for Hochiki Europe products. Design, installation, commissioning, maintenance and modification of fire detection and alarm systems should be carried out by, or under the responsibility of, a competent person in accordance with the applicable standards (for example BS 5839-1 in the UK). Statutory requirements imposed by the relevant enforcing authority also apply. Always refer to the current product manual and data sheet for the exact model before carrying out any work.
References
- CHQ-POM Installation Instructions, 2-3-0-703 (Issue 6)
- CHQ-POM Specification (Issue 4)
- CHQ-POM Connections drawing (conventional FIREbeam and FIRElink)
- POM to Conventional FIREbeam Wire Configuration Diagram
- FIREbeam Xtra Installation Manual, 2-3-0-2700 (Issue 1, December 2018)
- ESP FIREbeam Xtra Specification (Issue 7)