What replaces the discontinued SLR-E-IS intrinsically safe smoke detector?
The SLR-E-IS is replaced by the SOC-E-IS, which uses the same YBN-R/4IS base. Check the barrier, the IS documents and any SIL requirement before you order.
Direct answer
The SLR-E-IS intrinsically safe conventional optical smoke detector (also written SLR-E3-IS) was discontinued in 2020 and is replaced by the SOC-E-IS. Hochiki states that the specification is virtually identical and that the SOC-E-IS uses the same YBN-R/4IS intrinsically safe base. Before you order, check that the Zener diode barrier or galvanic isolator that feeds the zone meets the system drawing in the SOC-E-IS installation instructions, and check the intrinsic safety documentation for the installation. If the installed detector is a SIL-assessed version, contact Hochiki Europe technical support first, because the SOC-E-IS documents do not state a SIL assessment.
Applies to
- Products / Models: SLR-E-IS (SLR-E3-IS), discontinued; SOC-E-IS and SOC-E-IS(WHT) with the YBN-R/4IS base (also written YBN-R/4(IS))
- Firmware / Version: Not applicable
- Region: UK / Europe
- Standards: SOC-E-IS: BS EN 54-7 (LPCB); ATEX Ex ia IIC T5 Ga, certificate BASEEFA19ATEX0143X
What changes with the SOC-E-IS
- Base: the SOC-E-IS uses the same YBN-R/4IS base as the SLR-E-IS.
- Specification: Hochiki states that the specification is virtually identical.
- Drift compensation: the SOC-E-IS adds Automatic Sensitivity Window Verification (ASWV) drift compensation.
- Appearance: the SOC-E-IS looks different from the SLR-E-IS.
- SIL: the SOC-E-IS documents do not state a SIL assessment.
Resolution
- Identify the exact model code. Read the full code from the product label, including any suffix, because a suffix can change the base, the approvals or the assessment that the installation relies on.
- Check whether the installation relies on a SIL-assessed detector. If it does, contact Hochiki Europe technical support before you order a replacement.
- Confirm the intrinsically safe circuit. Check that the Zener diode barrier or galvanic isolator that feeds the zone meets the system drawing in the SOC-E-IS installation instructions, and check the intrinsic safety documentation for the installation, including the ATEX certification of the new detector. A zone monitor such as the CHQ-DZM(SCI)-IS is not itself intrinsically safe. It is installed in the safe area together with the barrier and does not replace it. See Which intrinsic safety barrier can I use with the SOC-E-IS and YBN-R/4IS?
- Fit the SOC-E-IS to the existing base. Follow the SOC-E-IS installation instructions. See How do I install a SOC-E-IS smoke detector in a hazardous area? The YBN-R/4IS base does not provide line continuity, so removing the old detector disconnects the devices beyond it on the zone until the new detector is fitted. Plan the work with the person responsible for the system.
- Remove the dust cover and test the detector. The detector does not operate until the dust cover supplied with it is removed. Test the detector with suitable test equipment, because certain types of test equipment should not be used in flammable or combustible atmospheres. The SOC-E-IS also has a magnetic test facility that can be operated with a suitable magnet. Follow the SOC-E-IS installation instructions.
- Record the change. Update the system and hazardous area records with the new detector model, and check that the system label required by the SOC-E-IS installation instructions still matches the installed equipment.
When to contact technical support
Contact Hochiki Europe technical support if the installed detector is a SIL-assessed version, if the barrier or isolator in the installation does not meet the system drawing in the SOC-E-IS installation instructions, or if the base fitted is not the YBN-R/4IS. Have the full model code and a photograph of the label ready.
Safety note
This article is general guidance for Hochiki Europe products. Design, installation, commissioning, maintenance and modification of fire detection and alarm systems should be carried out by, or under the responsibility of, a competent person in accordance with the applicable standards (for example BS 5839-1 in the UK). Statutory requirements imposed by the relevant enforcing authority also apply. Always refer to the current product manual and data sheet for the exact model before carrying out any work.
References
- SOC-E-IS Intrinsically Safe Conventional Smoke Detector specification (ISS6)
- YBN-R/4IS Intrinsically Safe Base specification (ISS4)
- CHQ-DZM(SCI)-IS Intrinsically Safe Dual Zone Monitor specification (ISS4)
- How do I install a SOC-E-IS smoke detector in a hazardous area?
- Which intrinsic safety barrier can I use with the SOC-E-IS and YBN-R/4IS?
Last reviewed: 2026-11-23 — Reviewed by: Hochiki Europe Technical Support