Which parts, junction boxes and end-of-line devices do I need for Hochiki LHDC?
Identify whether the LHDC is analogue or digital, then choose the matching interface unit, end-of-line device and junction boxes, and confirm the selection against the data sheet configuration diagrams.
Direct answer
The parts you need depend on which type of Hochiki linear heat detection cable (LHDC) is installed. Analogue LHDC (700-001LSOH, 700-005, 700-003, 700-004) needs an analogue interface unit such as the LDM-519-LP and an analogue end-of-line (EOL) device, for example 700-515. Digital LHDC (700-070, 700-071, 700-090, 700-091) needs a digital interface unit (LDM-519-DDL, LDM-519-DDLX or LDM-519-DIM) and the EOL device that matches that interface unit. Junction boxes and through connectors are available in stainless steel and polycarbonate. Confirm the selection against the configuration diagrams on the data sheets before ordering.
Applies to
- Products / Models: Analogue LHDC 700-001LSOH, 700-005, 700-003, 700-004; digital LHDC 700-070, 700-071, 700-090, 700-091, 700-180, 700-181; interface units LDM-519-LP, LDM-519-SEN-N, LDM-519-DDL, LDM-519-DDLX, LDM-519-DIM; EOL devices 700-502, 700-511, 700-515, 700-516, 700-518, 700-541, 700-572 to 700-576; junction boxes and through connectors 700-507, 700-508, 700-522, 700-523 and 700-525
- Firmware / Version: Not applicable
- Region: Not applicable
- Standards: Not applicable (check the current approvals for the specific cable on its data sheet before specifying)
Resolution / Steps
1. Identify the type of cable
The interface unit and the EOL device differ between the two types of cable, so identify the cable first. The part number is given on the cable data sheet.
- Analogue LHDC (resettable): red 700-001LSOH and black 700-003, and the stainless steel braided versions red 700-005 and black 700-004. The cable is recoverable and can be tested after an alarm. The alarm point is set on the interface unit and depends on the zone length.
- Digital LHDC (non-resettable): a twisted pair that operates at a fixed temperature and must be replaced where it has operated. 700-070 alarms at 70 °C (maximum ambient 45 °C), 700-090 at 90 °C (maximum ambient 70 °C) and 700-180 at 180 °C (maximum ambient 150 °C short term, 130 °C long term). The stainless steel armoured versions are 700-071, 700-091 and 700-181.
2. Choose the interface unit
| Cable | Interface unit | Use |
|---|---|---|
| Analogue | LDM-519-LP (700-201) | Analogue LHDC interface with an adjustable alarm set point. It can be connected to a conventional fire alarm panel zone or to an addressable loop through an interface module. |
| Analogue | LDM-519-SEN-N (700-305) | Analogue LHDC interface with two adjustable alarm levels and volt-free fire and fault relays. It needs its own 20 to 60 V DC supply (positive earthed). |
| Digital | LDM-519-DDL (700-451) | Digital LHDC interface with a display that shows the distance to the alarm point, for cable lengths up to 2 km. |
| Digital | LDM-519-DDLX (700-471) | As the LDM-519-DDL, for cable lengths up to 10 km. |
| Digital | LDM-519-DIM (700-441) | Digital interface monitor in a DIN rail format, with volt-free fire and fault contacts. |
The interface unit data sheets list 700-070, 700-071, 700-090 and 700-091 as the compatible digital cables. Contact Hochiki Europe Technical Support before specifying 700-180 or 700-181 with an interface unit. To connect an interface unit to a Hochiki addressable loop, the instructions show a Hochiki zone or input module, such as the CHQ-SIM or CHQ-POM. Application Note 205 also refers to the LDM-621-DDL, LDM-621-DDLX and LDM-519-DIM-28 interface units for non-resettable digital LHDC; these are not covered by the Issue 2 data sheets used in this article, so contact Hochiki Europe Technical Support for the cable and EOL device to use with them.
3. Choose the EOL device
The EOL device monitors the cable for faults. On analogue cable it monitors for open and short circuits; on digital cable it monitors for open circuits. In most installations the minimum requirement is that the LHDC circuit is monitored for disconnection by an EOL device together with an appropriate fire alarm channel or addressable loop interface unit.
| EOL enclosure | Analogue LHDC | Digital LHDC with LDM-519-DDL or DIM-28 |
|---|---|---|
| Stainless steel 316 with fire and fault test key switch | 700-515 | 700-574 |
| Stainless steel 316 without test | 700-518 | 700-575 |
| Die cast with fire and fault test switches | 700-511 | 700-573 |
| Polycarbonate | 700-502 | 700-572 |
| ABS with fire and fault test key switch | 700-541 | 700-576 |
For the LDM-519-SEN-N, use the ABS analogue EOL 700-541. The EOL data sheet does not list a separate EOL device for the LDM-519-DDLX, so contact Hochiki Europe Technical Support for this interface unit. The LDM-519-DDL and LDM-519-DIM are listed as legacy interface units on the current data sheet. For an existing LDM-519-DIM installation, contact Hochiki Europe Technical Support for the matching EOL device.
4. Choose junction boxes and through connectors
Junction boxes join lengths of LHDC, or connect the LHDC to the interposing cable from the interface unit. The EOL device is itself an enclosure fitted at the far end of the LHDC.
- Stainless steel 316: 700-522 (junction box for an interposing cable to LHDC), 700-523 (cable in plus LHDC loop) and 700-525 (LHDC through connector).
- Polycarbonate: 700-507 (junction box for an interposing cable to LHDC) and 700-508 (LHDC through connector).
Use the configuration diagrams on the EOL data sheet and the interface unit data sheet to confirm which junction boxes and EOL devices the installation needs. Fixings such as cable ties and T-clips are listed on the LHDC fixings data sheet.
When to contact technical support
Contact Hochiki Europe Technical Support or the sales team before ordering if the cable type cannot be identified, if the correct junction box or EOL device for a configuration is unclear, or for configurations not covered by this article, such as 180 °C digital cable or the LDM-519-DDLX and LDM-519-SEN-N interface units.
Safety note
This article is general guidance for Hochiki Europe products. Design, installation, commissioning, maintenance and modification of fire detection and alarm systems should be carried out by, or under the responsibility of, a competent person in accordance with the applicable standards (for example BS 5839-1 in the UK). Statutory requirements imposed by the relevant enforcing authority also apply. Always refer to the current product manual and data sheet for the exact model before carrying out any work.
References
- Analogue LHDC Cable Datasheet (Hochiki, Issue 2)
- Digital LHDC Cable Datasheet (Hochiki, Issue 2)
- EOL Terminators Datasheet (Hochiki, Issue 2)
- LDM-519-LP Datasheet (Hochiki, Issue 2)
- LDM-519-DDL Datasheet (Hochiki, Issue 2)
- LDM-519-DDLX Datasheet (Hochiki, Issue 2)
- LDM-519-DIM Datasheet (Hochiki, Issue 2)
- LHDC Fixings Datasheet (Hochiki, Issue 2)
Last reviewed: 2026-11-23 — Reviewed by: Hochiki Europe Technical Support