Why will Loop Explorer 2 (LE2) not connect to, or transfer a configuration to, my Latitude or Syncro AS panel?

Check that the LE2 database matches the panel firmware, refresh the licence and confirm the COM port.

Direct answer

When Loop Explorer 2 (LE2) will not connect to a Latitude, or Syncro AS panel, or will not transfer a configuration, the usual causes are a database that does not match the panel, a licence that has not been refreshed, a COM port problem, or panels on one network that hold different databases or firmware. Check the database and licence first, then the PC connection, then the network. If the panel type still shows as unknown, contact Hochiki Europe technical support.

Applies to

  • Products / Models: Loop Explorer 2 (LE2) configuration software; Latitude EN panels (LE2 database "Hochiki Europe Latitude"); Taktis and Syncro AS panels (LE2 database "Syncro & Taktis")
  • Firmware / Version: All versions. The LE2 version must be new enough for the panel firmware. For Latitude EN panels, for example, firmware EN-00.13.R004 needs LE2 3.440 or later.
  • Region: Not applicable
  • Standards: Not applicable

Symptoms

  • The Transfer Configuration screen cannot connect to the panel, or the panel transfer option is not available.
  • LE2 reports a licence problem.
  • LE2 shows an error message when you transfer a configuration.
  • LE2 shows the panel type as unknown, or reports "Failed to locate panel type for import".

Likely causes

  • The database selected in LE2 does not match the database the panel was built with.
  • A database has been added to your LE2 account, but the licence has not been checked since, so the database is not yet available in LE2.
  • The LE2 licence has expired, or the PC has no internet connection to refresh it.
  • The PC cable is not connected to the panel, or it is on a COM port that LE2 cannot use.
  • The memory write enable switch on the panel is not set to ON, so the panel does not accept the new configuration.
  • Panels on the same network hold different databases, firmware versions or configurations.

Resolution

  1. Check the LE2 version. Open Help and then About to read the LE2 version and the database name in use. Confirm that the LE2 version is new enough for the panel firmware. Panel firmware EN-00.13.R004, for example, needs LE2 3.440 or later.
  2. Select the database that the panel was built with. Go to Tools and then License. Under Database Name, select the database that matches the panel. For a Latitude panel supplied under the Hochiki Europe name this is Hochiki Europe Latitude. For a Taktis or Syncro AS panel it is Syncro & Taktis. The LE2 database must match the database of the panel. If you are not sure which database your panel uses, or the database is not in the list, contact Hochiki Europe technical support with the panel firmware version.
  3. Refresh the licence. With the PC connected to the internet, select Check Now in the License window and sign in with your own LE2 account details if you are asked. A new licence with a date in the future should be returned. Then select Get Update Now for the database you chose. LE2 shows a confirmation message when the database has updated. If you see no confirmation, go to Edit Preferences, select Updates and then Check Now, and try again. Once the licence has been refreshed, LE2 needs an internet connection only to update the licence, download updates or change the password. If the database you need is not in the list, contact Hochiki Europe technical support.
  4. Check the PC connection and COM port. For a Latitude panel, connect a USB cable between the PC and the USB port on the panel. For a Syncro AS panel, connect the Syncro programming lead between the PC connector on the panel and a serial port on the PC, and use a USB-to-RS232 converter if the PC has no serial port. You do not need to put a Syncro AS panel into a PC mode or fit any jumper links to transfer a configuration. In Tools and then Transfer Configuration, highlight the panel and select Connect to Panel. LE2 shows a tick when the connection is established. If LE2 still cannot connect, open Ports (COM & LPT) in Windows Device Manager and note the COM port number given to the cable or converter. On a Syncro AS panel, also try a different USB-to-RS232 converter. If LE2 still cannot connect, contact Hochiki Europe technical support with the COM port number.
  5. Set the write enable switch and check the transfer direction. Before you transfer a configuration to the panel, set the memory write enable switch on the panel to ON. Set it back to OFF when the transfer has finished, then clear the resulting system fault at the panel. Before you select Transfer to Panel, confirm that the direction arrow at the bottom of the screen points the way you intend.
  6. Bring every panel on a network onto the same database, firmware and configuration. Every panel on a Latitude network has to hold the same configuration (see the related article below) and run the same firmware version. If the panels on one network were built with different databases, contact Hochiki Europe technical support before you change anything. Technical support supplies the firmware files and the instructions. Flashing a panel erases its configuration, and the panel does not monitor the system during the update or the autolearns that follow. Before you start any of this work, agree it with the responsible person and make alternative arrangements for monitoring. When the configuration has been transferred back, test the system before you return it to normal monitoring. Before any panel is flashed, save each panel's configuration. Where LE2 can connect to the panel, use Transfer to PC in LE2. On a Latitude panel, you can also save the configuration to a USB memory stick as an XML file and import it into LE2. To do this, set the memory write enable switch on the display card to ON, log in at access level 3, and export the configuration from Engineer Options. Set the switch back to OFF when the file has been saved. For a Syncro AS panel, ask Hochiki Europe technical support how to save the configuration. When you import the XML files into LE2, save the LE2 file under a new file name and do not overwrite your original file. Then flash the panels only as Hochiki Europe technical support instructs.

When to contact technical support

Contact Hochiki Europe technical support if:

  • you are not sure which database your panel uses;
  • the database you need is not listed under Database Name;
  • LE2 still reports no licence after Check Now;
  • LE2 still cannot connect after you have checked the COM port;
  • the panel type still shows as unknown after the database and firmware have been matched;
  • panels on one network cannot be brought onto the same database and firmware.

Have the panel firmware version and the LE2 version ready. Software and firmware files are available from Hochiki Europe technical support. To receive them, you must have completed Hochiki Europe face-to-face training.

Safety note

This article is general guidance for Hochiki Europe products. Design, installation, commissioning, maintenance and modification of fire detection and alarm systems should be carried out by, or under the responsibility of, a competent person in accordance with the applicable standards (for example BS 5839-1 in the UK). Statutory requirements imposed by the relevant enforcing authority also apply. Always refer to the current product manual and data sheet for the exact model before carrying out any work.

References

Last reviewed: 2026-11-23 — Reviewed by: Hochiki Europe Technical Support