Why does my FIREbeam fail to auto-align or show a fluctuating air quality reading?

Failed auto-alignment or a fluctuating AQ on an ESP FIREbeam Xtra, CDX FIREbeam Xtra or ESP FIREbeam is usually caused by reflections from something other than the reflector, so fix the background, repeat pre-alignment and reach the required AQ before auto-alignment.

Direct answer

When an ESP FIREbeam Xtra, CDX FIREbeam Xtra or ESP FIREbeam will not complete auto-alignment, or its air quality (AQ) reading fluctuates, the usual cause is infrared light returning from something other than the reflector, such as a shiny, white or glass wall, metal cladding or an object close to the beam path. Give the reflector a non-reflective background, repeat pre-alignment with the reflector covered, and reach the manual-alignment AQ the manual requires (over 40% on ESP FIREbeam, at least 80 to 100% on FIREbeam Xtra, ideally above 100%) before auto-alignment. Then confirm with a fault test at the reflector.

Applies to

  • Products / Models: ESP FIREbeam Xtra (reflective optical beam smoke detector with low-level controller, installation manual 2-3-0-2700) with its 70KIT140 and 140KIT160 range extension kits, SHORT RM short-range mask, WINDOW-AC anti-condensation window and REF-AC anti-condensation reflector; CDX FIREbeam Xtra (conventional version with the same controller); ESP FIREbeam (earlier model, installation manual 2-3-0-1340) with its 40KIT80 and 80KIT100 range kits. Not applicable to the CDX FIREbeam Conex, which is a conventional, app-configured device. For any value that is specific to your model, follow the installation manual for that model.
  • Firmware / Version: Not applicable
  • Region: Not applicable
  • Standards: ESP FIREbeam Xtra — EN 54-12:2015 (optical beam line smoke detectors)

Symptoms

  • During pre-alignment, with the reflector covered, the output power (IR power) stops rising early, or the AQ figure rises and fluctuates between about 5% and 10%.
  • In manual alignment, the AQ does not jump when the reflector is uncovered, or it stays below the level needed to start auto-alignment.
  • Auto-alignment runs for much longer than expected, shows Align aborted, or the X and Y positions drift away from the reflector.
  • When the whole reflector is covered for the fault test, the beam does not go into FAULT. On ESP FIREbeam, the AQ also does not fall to 10% or below.
  • In service, the AQ wanders, ALIGN appears repeatedly, or the beam loses the reflector after a scheduled auto-alignment.

Likely causes

  • A reflective background around or behind the reflector, such as a shiny, white or glass wall, painted metal or metal cladding. The beam cannot distinguish the edges of the reflector from the background, so auto-alignment cannot centre on it.
  • Objects close to the beam path or near the head, such as structural steel, racking, stored goods, ceiling fans or access equipment. During pre-alignment the beam treats the first strong reflection as the far wall.
  • The reflector was visible during pre-alignment. The power levels are then set from the reflector instead of the far wall.
  • Auto-alignment was started before manual alignment reached the required AQ.
  • Direct sunlight shining into the head, for example through a glass atrium or roof light. Ambient sunlight does not affect the beam.
  • Two or more beams facing each other that are set to the same Phase, which can cause unreliable readings.
  • Dirt, a film left after cleaning, or condensation on the lens or the reflector.
  • A distance that does not match the reflector arrangement, for example no short-range mask on a FIREbeam Xtra under 20 metres.
  • A head whose X or Y position does not change when it is commanded to move.

Resolution

  1. Check the distance and the clear space. The current data sheet gives 7 to 70 metres for the standard FIREbeam Xtra (70 to 140 metres with the mid-range kit, 140 to 160 metres with the long-range kit), and the short-range mask should be fitted to the single reflector below 20 metres. The standard ESP FIREbeam covers 5 to 40 metres (40 to 80 metres and 80 to 100 metres with the range kits). For FIREbeam Xtra, keep 1 m of clear space along the beam path and 500 mm around the edges of the reflector. For ESP FIREbeam, the beam must see at least 200 mm of clear space around the reflector. Mount the reflector square to the beam: the reflector tolerates a misalignment of only ±2°.
  2. Give the reflector a non-reflective background. If the wall behind the reflector is shiny or glass, mount the reflector on a piece of non-reflective material approximately 1 m across, such as MDF, with a dark matt finish. To find a suspected reflection, temporarily cover the surface or object with dark, non-reflective material such as cardboard and watch whether the readings improve.
  3. Repeat pre-alignment with the reflector covered. Cover the reflector with a non-reflective black cloth or similar, or do not fit it yet; the FIREbeam Xtra cannot be commissioned if the reflector can be seen. The manuals recommend fast commissioning mode in most cases. It moves the motors four times faster but draws 17 mA instead of 3.5 mA, so if the loop cannot supply the extra current for several beams at once, commission one beam at a time or use normal mode. During pre-alignment the receiver sensitivity (RX Sense) rises to 100% and then the IR power rises until the beam receives about 6% back from the far wall. If the IR power stops low, or the AQ fluctuates between about 5% and 10%, the beam is seeing a nearby object: use the X and Y keys to move the beam path away from it, or remove the obstruction. The ESP FIREbeam manual gives approximate IR power levels for each distance (for example about 10% at 10 m, 25% at 40 m and 50% at 70 m), and a reading noticeably below the table points to a nearby reflection. Where the far wall itself is white or shiny, a temporary dark target of approximately 2 m by 1 m, centred where the beam meets the wall, has helped pre-alignment complete.
  4. Align manually before auto-alignment. Uncover or fit the reflector. The AQ should jump (on FIREbeam Xtra it can reach about 135%). If it does not, move the beam in small steps with the X and Y keys and wait for the head to reach each position; the display shows the actual position stepping towards the requested one. Do not start auto-alignment until the AQ is over 40% on ESP FIREbeam, or at least 80 to 100% on FIREbeam Xtra; on both, aim for above 100%. Cover the reflector briefly to prove the AQ drops and that the beam is looking at the reflector.
  5. Run auto-alignment and leave the beam path clear. The beam reduces its power settings, finds all four edges of the reflector twice and then centres on it. The FIREbeam Xtra manual gives up to 10 minutes and does not give a separate time for normal mode; on ESP FIREbeam it takes about 3 minutes on average in fast mode and up to 30 minutes in normal mode. Align aborted means something crossed the beam path. If a FIREbeam Xtra has not finished after 10 minutes, check the X and Y figures: they should be below 1.50 on each axis and are normally below 0.90. If they are higher, return to manual alignment, bring both axes back to 0.00 and remove the obstruction before trying again.
  6. Prove the alignment with a fault test and a fire test at the reflector end. Testing at the reflector end confirms the beam is looking at the reflector. Cover the whole reflector within one second with a non-reflective card: the beam should report FAULT after the time to fault (10 seconds by default). On ESP FIREbeam, the AQ should also fall to 0% (10% at most). If the beam does not go into FAULT, infrared light is still returning from something other than the reflector, so go back to step 2. For the fire test, cover the reflector slowly (up to 70% on FIREbeam Xtra, half the reflector on ESP FIREbeam); the beam should report FIRE after the time to fire (10 seconds by default). Agree these tests with the people responsible for the building first, because a fire test generates a fire condition at the panel.
  7. If the AQ fluctuates in service, check the operating settings. In Beam Maintenance, read Dirt Comp: above +50%, clean the lens face and the reflectors without leaving a film, then run an auto-alignment to re-calibrate. Give beams that face each other different Phase settings (0 to 6). Shade the head from direct sunlight, and use the anti-condensation versions of the window and reflector where condensation occurs. In normal operation the beam re-aligns when the received signal stays below 90% for the Align Time (4 hours by default, adjustable from 0 to 12 hours), so a reflective background that is not corrected will disturb the beam again. Align On/Off in Mode Change can turn this automatic re-alignment off, but only do so when the head is on a sturdy fixing such as a brick wall or major structural steel; auto-alignment still works during commissioning.

When to contact technical support

Contact Hochiki Europe technical support if the beam still does not go into FAULT in the fault test after the background and obstructions have been dealt with, if auto-alignment still does not complete after the steps above, if you need guidance on adjusting IR Power and RX Sensitivity manually in the Diagnostics menu, or if the X or Y position does not change when commanded, which can indicate a fault in the head. Have the beam distance, the reflector arrangement, the AQ, IR power and RX sensitivity readings, and the X and Y figures ready. If the beam goes into fault every time the panel is reset, see Why does my ESP FIREbeam go into fault every time the panel is reset?

Safety note

This article is general guidance for Hochiki Europe products. Design, installation, commissioning, maintenance and modification of fire detection and alarm systems should be carried out by, or under the responsibility of, a competent person in accordance with the applicable standards (for example BS 5839-1 in the UK). Statutory requirements imposed by the relevant enforcing authority also apply. Always refer to the current product manual and data sheet for the exact model before carrying out any work.

References

Last reviewed: 2026-11-23 — Reviewed by: Hochiki Europe Technical Support