How do I diagnose a High Flow or Low Flow fault on a FIRElink-25 or FIRElink-100?
A High Flow or Low Flow fault means the airflow has left the learned limits: check the exhaust, the pipework and the flow limits in that order.
Direct answer
A High Flow or Low Flow fault on a FIRElink-25 or FIRElink-100 means that the airflow through the detector has moved outside the limits it learned at installation. High flow can point to a loose, cracked or broken pipe, or a missing end cap. Low flow can point to a blocked pipe. Check the exhaust first, then the pipework, then the Flow High Limit and Flow Low Limit in the Remote software. Change a limit only after the pipework has been proved sound, and confirm the change with Hochiki Europe technical support.
Applies to
- Products / Models: FIRElink-25 and FIRElink-100 aspirating smoke detectors
- Firmware / Version: All versions (the Flow Fault Delay setting needs Remote Control Software version 3.2 or later)
- Region: Not applicable
- Standards: EN 54-20
Symptoms
- The Fault LED on the detector is lit and a fault signal is sent to the fire alarm panel. The Fault LED is also lit when the detector is isolated, so check the event log in step 2.
- The event log records a flow fault. The detector stores the last 200 events, and a separator fault is logged in the same way, so confirm that the entry is a flow fault.
- The flow rate shown in the Remote software is above the Flow High Limit (High Flow) or below the Flow Low Limit (Low Flow).
Likely causes
- High Flow: a sampling pipe that is not pushed home into the inlet, or a pipe that is broken or cracked.
- High Flow: a pipe run with no end cap. Open bore pipes are not recommended.
- Low Flow: a blocked sampling pipe, for example after building work close to the sampling pipes.
- Either: an exhaust that is blocked, or a detector that exhausts into a different air pressure zone from the sampling holes (see Why does my FIRElink-25 or FIRElink-100 report a flow fault when it is mounted in a different air pressure zone?).
- Either: a Flow High Limit that is set too low or a Flow Low Limit that is set too high.
- Either: a change to the sampling pipe network after the detector learned its flow setup.
Resolution
- Agree the panel arrangements. Before you start, agree with the responsible person how the detector is to be treated at the fire alarm panel while you work, because the tests and setting changes below can send fault signals to the panel.
- Confirm which fault it is. Open the event log in the Remote software and check that the entry is a flow fault and not a separator fault. Then use the Read button in the Diagnostics screen to see the detector output and flow rate update in real time, and note whether the flow rate is above the high limit or below the low limit.
- Check the exhaust. The exhaust air from the detector must not be impeded in any way. Make sure that the protective bung is not fitted in the exhaust port. If the detector is in a different air pressure zone from the sampling holes, follow the article linked under Likely causes.
- For High Flow, inspect the pipework. Check that each pipe is pushed firmly home into its inlet and is not broken or cracked. Check that every pipe run is fitted with an end cap, drilled to the size shown in the pipe design (normally 4 mm or 5 mm and free from burrs). Check that the joints are airtight. Do not use cement or glue where the pipe enters the detector inlet: the pipe should be firmly twisted into the inlet.
- For Low Flow, look for a blockage. Check the pipe that gives the error, from the detector to the end cap, for debris, crushing or damage from nearby building work, and clear it.
- Compare the pipework with the design. Added or enlarged sampling holes, a changed pipe route or a different pipe length change the flow. If the installed network differs from the design, refer back to the designer, because a revised PipeCAD model may be needed.
- Check the flow limits. Open the Flow Monitoring tab in the Remote software. The High and Low limits are set up automatically at the first power-up. Check that the Flow Low Limit is not set too high and that the Flow High Limit is not set too low for the normal flow rate of the pipe. Do not change a limit until steps 3 to 6 are complete, because widening a limit can hide a genuine pipe fault. The default limits are set to meet the airflow monitoring requirements of EN 54-20, so confirm any change with Hochiki Europe technical support first.
- Prove the repair. Run the Diagnostics in the Remote software. If latching faults are enabled, reset the detector so that the fault clears, then watch the flow rate to confirm that it stays between the two limits.
When to contact technical support
Contact Hochiki Europe technical support if the flow fault returns after the exhaust, the pipework and the flow limits have been checked, if the pipe network has been changed from the design and the detector no longer holds its flow, before you change a flow limit, or if you need Remote Control Software version 3.2 or later. Have the detector model, the pipe layout and the event log ready.
Safety note
This article is general guidance for Hochiki Europe products. Design, installation, commissioning, maintenance and modification of fire detection and alarm systems should be carried out by, or under the responsibility of, a competent person in accordance with the applicable standards (for example BS 5839-1 in the UK). Statutory requirements imposed by the relevant enforcing authority also apply. Always refer to the current product manual and data sheet for the exact model before carrying out any work.
References
- FIRElink-25 Installation Manual (9-5-0-344, ISS5)
- FIRElink-100 Installation Manual (9-5-0-345, ISS5)
- Application Note 149: Construction of a Sampling Pipe Network (ISS1)
- Why does my FIRElink-25 or FIRElink-100 report a flow fault when it is mounted in a different air pressure zone?
Last reviewed: 2026-11-23 — Reviewed by: Hochiki Europe Technical Support