Why does my CHQ relay output not operate, or operate on every fire, on a Latitude panel?

A CHQ relay output is in Default Ring mode by default, which follows the panel default ring mode for a fire, until Def Ring Mode (Fire) is unticked and a cause and effect controls it.

Direct answer

A CHQ-DRC2(SCI), CHQ-MRC2(SCI)S|X or CHQ-PCM(SCI) relay output on a Latitude panel is in Default Ring mode when it is added, unless it has been programmed otherwise, and then it switches on for a fire condition and does nothing else. With the panel default ring mode set to Common that means every fire; Zonal and Two Stage follow their own patterns. Once Def Ring Mode (Fire) is unticked in Loop Explorer 2 (LE2), only a cause and effect operates the relay. Check which mode the output is in, then check that the cause and effect matches the event you are testing.

Applies to

  • Products / Models: CHQ-DRC2(SCI), CHQ-MRC2(SCI) and CHQ-PCM(SCI) relay outputs, on Latitude EN addressable control panels configured with Loop Explorer 2 (LE2)
  • Firmware / Version: Zone test behaviour (step 8) depends on the panel firmware version. Check the version installed on the panel.
  • Region: Not applicable
  • Standards: BS EN 54-17 (short-circuit isolators), BS EN 54-18 (input/output devices)

Symptoms

  • A relay does not operate when a detector or call point goes into fire.
  • A relay operates on every fire on the panel, when it should operate only for certain devices or zones.
  • A relay still operates while one or more zones are in test.
  • A relay stopped operating after a cause and effect was added or the configuration was changed.
  • A relay that is meant to signal a fault operates on fire.

Likely causes

  • Def Ring Mode (Fire) is still ticked on an output that was meant to be controlled by a cause and effect. The relay then follows the panel default ring mode for a fire condition and ignores the cause and effect logic.
  • Def Ring Mode (Fire) has been unticked but no cause and effect operates the output, or the cause and effect uses a different input, operator or output from the one you are testing.
  • The input that is meant to cause the effect has an input action that the cause and effect is not written for. Transparent, for example, is the action meant for controlling outputs through cause and effect.
  • A relay that is meant to signal a fault is still ticked for Def Ring Mode (Fire), so it operates on a fire.
  • The output has a delay, Alarm Silence, Invert Output or Duration setting that changes when and for how long it operates.
  • The output has been disabled at the panel.
  • A cause and effect is driving the relay during a zone test, because the relay is no longer in Default Ring mode.

Resolution

  1. Plan the test. A CHQ relay output usually switches real equipment such as plant shutdown, dampers, door holders or a signal to another system, so every test operates that equipment. Agree the test with the people responsible for the building, isolate or notify anything that must not operate, including the alarm receiving centre and any fire routing, because a test that creates a fire condition can send a signal to it. Follow How to disable part of a fire alarm system safely. Changing a configuration file is a modification to the system, so read the section "Before you change the configuration" in the ESP FIREbeam article Why does my ESP FIREbeam go into fault every time the panel is reset? (it applies to any configuration change) before you save anything.
  2. Decide what the relay is meant to do. There are four common jobs: operate on every fire, operate on fire only under certain conditions, signal a fault, or respond to another event such as a pre-alarm or a technical alarm. The settings in the next steps depend on which one you need.
  3. Open the output properties in LE2. Before you change anything, download the current configuration from the panel into LE2 and keep a copy of it, so that you are editing what is running on site and can restore it if the change does not give the result you want. Obtain LE2 from Hochiki Europe technical support. Open the project for the panel, select the relay and read its properties. The key box is Def Ring Mode (Fire), which some LE2 versions label Default Ring Mode (Fire). When it is ticked, the output switches on for a fire condition as set by the default ring mode on the panel settings. When it is unticked, only a cause and effect (or another output option that you have ticked) operates the output.
  4. Set the mode to match the job. For a relay that must operate on any fire alarm activation, tick Def Ring Mode (Fire) and leave the other options unticked. For a relay that must operate only under conditions, untick Def Ring Mode (Fire) and write a cause and effect for it. For a relay that must signal a fault, contact Hochiki Europe technical support for the correct setting.
  5. Check the cause and effect. In LE2, open the Cause and Effect tab and check that the input chosen as the cause is the device or zone you are testing, that the operator is correct, that the output ticked is the relay you are checking, and that Continuous or Intermittent is as intended. Each cause and effect needs its own name. Then check the input action of the cause device. The available actions include Fire, Fault, Pre-Alarm, Technical Alarm, Security, Transparent, Disablement and Test Mode, and a cause device whose input action is not the one the cause and effect is written for will not give the effect you expect.
  6. Check the other output options. Read the output options for a global or individual delay (each stage can be up to 10 minutes), Alarm Silence (the output goes inactive when Silence Alarms is pressed), Invert Output (the output turns off when activated) and Duration (the output stays active for a set time only). Any of these can make a correctly programmed relay look as if it has not operated. Then check at the panel that the output has not been disabled: the Latitude user controls include Disable /Enable All Outputs, All Plant Outputs and individual Panel Outputs.
  7. Plan for zone test. An output that is operated by a cause and effect continues to operate while a zone is in test, because it is no longer in Default Ring mode. To test a zone without operating plant, disable the outputs first, using the user controls on the panel or a function button that disables outputs, or a Disablement input with a cause and effect that disables the relevant outputs. Disabling the outputs also stops outputs that a cause and effect operates. Check that the outputs show as disabled on the panel before the first zone test. Restore the zones and re-enable the outputs as soon as the test is finished, and record the test in the log book.
  8. Save, send and retest. Save the configuration, send it to the panel, keep the previous configuration with the system documentation, and repeat the test with the relay isolated from live equipment where possible, then once more with the equipment connected. If the module itself reports a fault, resolve that first: see Why do several devices on my addressable loop report random communication faults?.

For the relay ratings of each module and how to choose between them, see Which Hochiki CHQ output module should I use?. A CHQ-DSC2(SCI) drives sounders rather than relays and needs its own auxiliary supply, which is covered in Which Hochiki CHQ modules need an external 24 V PSU?.

When to contact technical support

Contact Hochiki Europe technical support if the relay still does not behave as intended after the mode, the cause and effect, the output options and the disablement state have been checked, if you do not have the LE2 project for the panel, or if the output is connected to equipment on another fire alarm panel and a signal from that panel makes your relay operate when it should not. Have the panel type, the firmware version and the configuration file ready.

Safety note

This article is general guidance for Hochiki Europe products. Design, installation, commissioning, maintenance and modification of fire detection and alarm systems should be carried out by, or under the responsibility of, a competent person in accordance with the applicable standards (for example BS 5839-1 in the UK). Statutory requirements imposed by the relevant enforcing authority also apply. Always refer to the current product manual and data sheet for the exact model before carrying out any work.

References

Last reviewed: 2026-11-23 — Reviewed by: Hochiki Europe Technical Support