Should I use an ACC-EN or an ACD-EN multi-sensor, and which mode should I choose?

Use the ACC-EN for heat-enhanced smoke detection, or the ACD-EN when you need smoke, heat and CO combinations, day and night modes, or the CO and COHb functions.

Direct answer

Choose the ACC-EN when you want a smoke detector that becomes more sensitive as the temperature rises, or a plain smoke-only or heat-only detector. Choose the ACD-EN when you need a defined mix of smoke, heat and carbon monoxide (CO) sensing, separate day and night modes, or the CO and COHb functions. The ACC-EN has three panel-selected modes. The ACD-EN has 24 EN 54 approved modes and leaves the factory in mode 9A, which raises no separate heat or CO alarm. Check that your control panel supports the ACD-EN before you specify it.

Applies to

  • Products / Models: ACC-EN, ACC-EN(WHT), ACC-EN(BLK) (ESP multi-sensor); ACD-EN, ACD-EN(WHT) (ESP multi-sensor with CO)
  • Firmware / Version: All versions. The behaviour depends on the mode set at the control panel.
  • Region: UK / Europe
  • Standards: ACC-EN: EN 54-5 and EN 54-7, LPCB and VdS classes A1 and C (the ACC-EN specification, ISS5, lists EN 54-29 as approval pending). ACD-EN: EN 54-5, EN 54-7, EN 54-26, EN 54-29, EN 54-30, EN 54-31 and CEA 4021, depending on the mode selected.

Steps

  1. Decide whether you need CO sensing. Only the ACD-EN has a CO element. If the application needs a CO alarm, a COHb (carboxyhaemoglobin) toxic-threat function, or a CO-led fire decision, use the ACD-EN. CO sensing therefore means choosing an ACD-EN mode that includes it. Do not use a mode in which CO makes the fire decision where CO can be present in normal use, for example where there are vehicle exhaust fumes or in a badly ventilated kitchen. A CO-only mode is not a direct replacement for smoke detection.
  2. Check the panel. Both sensors need a compatible control panel, and the mode and any day and night changeover are set at the panel. Application Note 169 (ISS2, October 2021) lists the panels that support the ACD and tells you to confirm the extent of support with each panel manufacturer. Do not specify an ACD-EN mode until the panel manufacturer has confirmed that the mode can be selected.
  3. Check the sensor version you need. The ACC-EN is also made in marine, railway, SIL capable and SCI versions. The ACD-EN is not made in any of the above versions, so use an ACC-EN version for these applications.
  4. Pick the sensor and mode for the environment. Use the groups below. If the ACC-EN is enough, pick one of its three modes. If you need the ACD-EN, start from the mode groups and the example day and night pairs, then confirm the choice with the risk assessment.
  5. Record the choice. Note the mode, and the day and night modes where they differ, for every device, together with the reason for each choice. Heat and smoke detectors have different spacing rules. If either the day mode or the night mode is a heat-only mode, position the device to the spacing for heat detectors, and recheck the design before changing a device from a smoke mode to a heat mode.

ACC-EN: three modes

  • Smoke / heat combined (the default). The sensor works as an optical smoke detector, and its sensitivity is enhanced when the heat element sees a temperature rise above 40 °C. It cannot raise a fire condition from heat alone, so a heat-only test will not alarm it in this mode. Typical uses in Application Note 138: offices, hotel rooms, hospital wards, halls and cleanrooms.
  • Smoke only. Typical uses: offices and corridors.
  • Heat only. Approved by LPCB and VdS to classes A1 and C (EN 54-5 now calls these categories). The heat element alone makes the fire decision. Typical uses in Application Note 138: kitchens, laundries, boiler rooms, warehouse loading bays where vehicle fumes are present, and areas with airborne contaminants such as dust. Installation standards space heat sensors differently from smoke sensors, so check the spacing before you change a sensor from a smoke mode to heat only.

In its default mode, the ACC-EN is therefore a smoke detector with heat enhancement, not a detector in which heat or smoke can each raise the alarm on its own. For changing the heat threshold and optical sensitivity, see How do I change the sensitivity or heat threshold on an ALN-EN or ACC-EN sensor?.

ACD-EN: mode groups

In an ACD-EN mode code, a plus sign marks an element that makes the fire decision, and a slash marks an element that works in unison with the primary element. Application Note 152 lists all 24 modes. They fall into these groups:

  • Smoke and heat in unison, no separate heat alarm: 9A (the default, smoke with fixed-temperature heat and CO, plus the reduced false alarm function), 80 and 81 (smoke with heat). In 9A the heat and CO elements only adjust the smoke threshold, so the panel does not show a heat or CO alarm.
  • Smoke only: 82 (with the reduced false alarm function) and 83.
  • Heat only: 87, 88 and 89 (classes A1, A1R and A1S), and 8A, 8B and 8C (classes C, CR and CS). These use fixed-temperature and, in most of them, rate-of-rise heat.
  • CO and COHb: 9D (CO only), 9C (COHb only), 8F (smoke with COHb), 8E (smoke and fixed-temperature heat in unison, with COHb), and 93 to 98 (the heat classes above with COHb). 9B uses CO together with rate-of-rise heat (+CO/RoR in Application Note 152).
  • Everything active: 8D (smoke, fixed-temperature heat, rate-of-rise heat, CO and COHb) and 99 (smoke, heat and CO in unison; smoke, fixed-temperature heat, rate-of-rise heat and CO can each also decide on their own, and the COHb function is active, listed as +CO/COHb in Application Note 152).

The COHb function weighs CO concentration against time. The ACD-EN Technical Overview (see References) quotes the EN 50291 alarm requirements as a reference: no alarm before 120 minutes at 30 ppm, an alarm between 60 and 90 minutes at 50 ppm, between 10 and 40 minutes at 100 ppm, and within 3 minutes at 300 ppm. These figures describe the EN 50291 requirements for reference only. The ACD-EN specification lists EN 54 approvals and does not list EN 50291, so do not treat the COHb function as a replacement for a CO alarm that another standard or regulation requires. For what the ACD-EN detects and how the elements work, see What does the ACD-EN multi-sensor detect, and how does its CO, smoke and heat functions work?.

Example day and night modes

Application Note 152 gives a recommended day and night mode for each room type, as a guide only. A selection:

  • Hotel room: 8D by day and 8D at night.
  • Hospital common areas: 99 and 99.
  • Care home: 99 by day and 8D at night.
  • Bathroom or toilet: 87 by day and 80 at night.
  • Kitchen: 89 by day and 80 at night.
  • Hallway or corridor: 82 by day and 83 at night.
  • Office: 9A and 9A.
  • Boiler room and warehouse: 89 and 89.

The switch between the day mode and the night mode is a control panel function. Set the changeover times in the panel, following the panel manufacturer's documentation.

Testing the element you chose

A test only alarms the sensor if the element you stimulate can make the fire decision in the mode that is set. In a mode where an element only enhances the smoke decision, such as 9A, the heat and CO elements do not raise a separate alarm, so a single-stimulus test may not produce a CO or heat alarm. Application Note 204 gives the test equipment and the test procedure for the ACD and the ACC. For the ACD, it describes CO test gas and a Testifire unit with a CO capsule, which can test the smoke, heat and CO elements separately; the polling LEDs flash once, twice or three times to show which element is being tested. If you need the panel to show a CO alarm from a sensor set to a mode in which CO does not make the decision, ask Hochiki Europe technical support which mode to use for the test. Record any temporary mode change and restore the working mode afterwards.

When to contact technical support

Contact Hochiki Europe technical support if you are unsure which mode suits an environment, for example where there is vehicle exhaust, steam or tobacco smoke, if your panel is not on the Application Note 169 list, or if a sensor does not respond to a test in the mode you have set.

Safety note

This article is general guidance for Hochiki Europe products. Design, installation, commissioning, maintenance and modification of fire detection and alarm systems should be carried out by, or under the responsibility of, a competent person in accordance with the applicable standards (for example BS 5839-1 in the UK). Statutory requirements imposed by the relevant enforcing authority also apply. Always refer to the current product manual and data sheet for the exact model before carrying out any work.